You might also like
Triac 2 A
24 V DC
with minus plug link
24 V DC
with minus plug link
General data
Test isolation voltage | 2.5 kV |
---|---|
Mounting method | DIN-rail mountable TH35 or G32 (EN 60715) |
Housing | Black plastic, flame retardant |
Temperature range | -20...+60 °C |
Dimensions H×W×D | 68×12×82 mm |
Output
Switching voltage | 24...280 V AC |
---|---|
Switching current per output | 50 mA...2 A |
Saturation voltage (across output) | max. 1 V AC |
Leakage current (output is open) | max. 2 mA |
Switching time ON/OFF | 10/10 ms |
Switching frequency | max. 20/5 Hz (resist./ind.) |
Input
Voltage range ON | 10...35 V DC |
---|---|
Voltage range OFF | 0...3 V DC |
Input current | 6 mA |
Plug link (supplied) | Art-No. 90960 |
LED display | LED (red) |
Commercial data
country of origin | CZ |
---|---|
customs tariff number | 85414090 |
EAN | 4048879027953 |
eClass | 27371604 |
Packaging unit | 1 |