6 A (STOP1); 8 A (STOP0)
Protection-door and emergency-stop control
Light curtain control
Safety magnetic switch control
Automatic/manual/manual monitored reset/start
Protection-door and emergency-stop control
Light curtain control
Safety magnetic switch control
Automatic/manual/manual monitored reset/start

General data
Mounting method | DIN-rail mountable (EN 60715) |
---|---|
Temperature range | -25...+60 °C (storage temperature -40...+85 °C) |
Mech./ elect. life | 10 000 000 switching cycles/load dependent |
Connection | Spring clamp plug-in terminals |
Dimensions H×W×D | 100×22.5×121 mm |
Output
No. of alarm outputs | 1 - (Y1) |
---|---|
Contact material | Ag Sn O, self cleaning, positively driven |
Switching voltage | max. 250 V AC/DC |
No. of safety contacts | 2 - (13-14), (23-24), STOP0; 1 - (37-38), STOP1 |
No. of auxiliary contacts | 0 |
Switching current per output | max. 8 A (STOP0); max. 6 A (STOP1) |
Input
Input voltage | 24 V DC (-15 +20%), 24 V AC (-15 +10%) |
---|---|
Input current | 5.9 VA/2.4 W (with monitoring output) |
Utilization category
AC-15 | 6 A (230 V AC) STOP0; 3 A (230 V AC) STOP1 |
---|---|
Safety contacts (STOP 0) | max. 250 V AC/8 A; min. 5 V AC/5 mA (resist./ind.), at suitable suppression |
Safety contacts (STOP 1) | max. 250 V AC/6 A; min. 10 V AC/10 mA (resist./ind.), at suitable suppression |
DC-13 | 5 A (24 V DC) STOP0; 2 A (24 V DC) STOP1 |
Safety Indicators
DC | 99% (STOP0); min. 60% (STOP1) |
---|---|
Service life | 20 years |
Category | up to 4 (STOP0); up to 3 (STOP1) |
PL | up to e (STOP0); up to d (STOP1) |
SIL | up to 3 (STOP0); up to 2 (STOP1) |
Commercial data
country of origin | DE |
---|---|
customs tariff number | 85364900 |
EAN | 4048879367615 |
eClass | 27371819 |
Packaging unit | 1.000 |