You might also like
Expansion module
AO2 - (E) 4× M12 (I)
Current
AO2 - (E) 4× M12 (I)
Current
General data
Protection | IP20 |
---|---|
Connection | Spring clamp plug-in terminals: max. 1.5 mm² (AWG 16) |
Mounting method | DIN-rail mountable (EN 60715) |
Temperature range | 0...+60 °C (storage temperature -25...+70 °C) |
Dimensions H×W×D | 109×12.9×76.5 mm |
Technical Data
Operating voltage | 24 V DC (20.4...28.8 V DC) |
---|
Output
Conversion time (analog) | 200 µs (all channels) |
---|---|
Resolution (analog) | 15 Bit + sign |
Accuracy | max. 0.5% |
Galvanic isolation | 500 V DC between inputs and internal communication |
Internal communication
Module supply | via system connection |
---|---|
Current consumption | max. 60 mA from system, max. 25 mA externally (UI), idle load |
Current outputs
Load | max. 350 Ω |
---|---|
Input range | 0...20 mA, 4...20 mA |
Diagnostic
Communication status | via LED |
---|---|
Diagnostic via LED | per module and channel |
Diagnostic via BUS | per module |
Monitoring - under voltage | yes |
Monitoring - no voltage | no |
Short-circuit and overload | yes |
Actuator warning | per module via LED and BUS |
Wire break upper/lower limit overload | per module via LED and BUS |
Commercial data
country of origin | TH |
---|---|
customs tariff number | 85389099 |
EAN | 4048879562881 |
eClass | 27242601 |
Packaging unit | 1 |