You might also like
Digital inputs/outputs
DO4 DO4 DIO4 DIO4 (K3)
PROFIBUS 12 Mbit/s; M12, B-coded
7/8", 5-pole, max. 9 A
M12, 5-pole, A-coded
Output groups up to PLd (EN ISO 13849-1) can be switched off via safety relays
Connection cables are in the online shop under "Connection Technology".
Housing fully potted.
DO4 DO4 DIO4 DIO4 (K3)
PROFIBUS 12 Mbit/s; M12, B-coded
7/8", 5-pole, max. 9 A
M12, 5-pole, A-coded
Output groups up to PLd (EN ISO 13849-1) can be switched off via safety relays
Connection cables are in the online shop under "Connection Technology".
Housing fully potted.
Input
Sensor supply US | 24 V DC (EN 61131-2), max. 200 mA (M12 female), short-circuit and overload protected |
---|---|
Type | for 3-wire sensors or mechanical switches, PNP |
Connections
Fieldbus | PROFIBUS 12 Mbit/s; M12, B-coded |
---|---|
Sensor-system/actuator supply | 7/8", 5-pole, max. 9 A, safe circuits (1 + 2) via separate 7/8" supply (yellow), 2-pole disconnectable |
I/O ports | M12, 5-pole, A-coded |
PROFIBUS
Addressing | Rotary switch 1...99 |
---|
General data
Protection | IP67 |
---|---|
Mounting method | 2-hole screw mounting |
Temperature range | 0...+55 °C (storage temperature -20...+70 °C) |
Dimensions H×W×D | 39×63×225 mm |
Output
Actuator supply UA | 24 V DC (EN 61131-2), 3 circuits, (max. 9 A) |
---|---|
Switching current per output | max. 1.6 A (short-circuit and overload protected) |
Lamp load | 10 W |
Safe output
Switching current by safe output | max. 2 A short-circuit and overload protected, (EN13849-1) PLd |
---|---|
M12 (yellow) PIN 4 | 2 safety circuits (UA1/UA2) with 2 digital outputs each (EN13849-1) PLd |
M12 (yellow) PIN 2 | 2 safety circuits (UA1/UA2) with 2 digital outputs each (EN13849-1) PLd |
Parameterization
PIN 4 | 4× input/output |
---|---|
PIN 2 | 4× Input/Output/Diagnostic |
Diagnostic
Communication status | via LED |
---|---|
Diagnostic via LED | per module and channel |
Diagnostic via BUS | per module and channel |
Monitoring - under voltage | yes |
Monitoring - no voltage | yes |
Short-circuit and overload | yes |
Actuator warning | per channel via LED and BUS |
Cable break | per port |
Commercial data
country of origin | DE |
---|---|
customs tariff number | 85389099 |
EAN | 4048879051606 |
eClass | 27242604 |
Packaging unit | 1 |